Lubri-Tect Neutralizes, Scavenges, Prevents Acid and Moisture in A/C and Refrigeration Systems
FOR PREVENTIVE / CONTINUAL SYSTEM PROTECTION
- LubriTect™ can be added to a non-contaminated or safe system and will continually protect from light acid contamination.
- Test system for acid contamination.
- If system is safe, use the application chart on back to determine the number of bottles of LubriTect™ required for light contamination.
- Add LubriTect™ into system’s high side or liquid line with a refrigeration oil charging pump or additive injection tool. Flush all LubriTect™ into system by following with a small amount of refrigeration oil. Do not overfill system.
- Return system to service.
NOTE: Not effective against gross contamination as the amount of LubriTect™ in the system could be overwhelmed by extremely high acid/moisture content.
FOR SYSTEMS WITH ACID CONTAMINATION WITHOUT COMPRESSOR BURNOUT:
- Replace driers and replace lubricant if necessary.
- Using the application chart on back, determine the number of bottles of LubriTect™ required depending on degree of contamination, light or heavy.
- Follow steps 6 & 7 below.
FOR COMPRESSOR BURNOUT:
- Remove and properly dispose of used refrigerant and lubricant.
- Determine cause of burnout.
- Flush system with suitable flushing solvent.
- Using the application chart on back, determine the number of bottles of LubriTect™ required for heavy contamination.
- Change out compressor, driers and other required components. Charge with proper amount of lubricant, evacuate and charge with refrigerant.
- Add LubriTect™ into system’s high side or liquid line with a refrigeration oil charging pump or additive injection tool. Flush all LubriTect™ into the system by following with a small amount of refrigeration oil. Do not overfill system.
- After several days of operation, verify system is acid free. Re-treat if needed.